FSM-CT/CF self-limiting heating cable (Ex) up to +85 °C

FSM-CT is installed in residential, public and commercial buildings and in industrial hazardous (Ex) zones. FSM-CF is installed in chemically hazardous zones, such as production of bitumen, oil products, food and industrial oils and other chemical materials, approved for use in both safe and hazardous areas.

FSM2-CT self-limiting heating cable of 11 W/m and 17 W/m output can be used for heating, temperature maintenance and frost protection of pipes. The cable is produced with nanotechnologies, ensuring durable benefits; it withstands the temperature of up to +85 °C (when turned off). It can be installed in residential, public and commercial buildings and within industrial hazardous (Ex) zones.

FSM2-CF cable can be installed within chemically hazardous zones, that of bitumen, oil products, food and industrial oils and other chemical products, because approved for use in both, safe and hazardous areas.

Installation: the cable is laid onto small diameter pipes under thermal insulation layer.

 

 Voltage  220/230V AC
 Output  11 W/m and 17 W/m (+10 °C)
Dimensions  10,5×5,9 mm
Overjacket  Thermoplastic (CT)
Fluoropolymer (CF)
Min. bending radius  20–25 mm
Max temperature:
• Cable switched on
• Cable switched off

+65 °C

+85 °C
Min. instal. temperature  –40 °C (CENELEC –20 °C)
Temperature class  T6
fsm lentele_EN

Maximum length of the cable (m) in one electrical circuit depending upon the temperature

Ambient temperature 11FSM 17FSM
230 V
6 A  10 A  16 A 20 A   6 A  10 A 16 A  20 A
+5 °C 76 126 128 54 88 102
0 °C 70 118 128 50 84 102
–20 °C 46 78 124 128 34 56 88 102
–40 °C 36 60 96 120 26 42 68 86

 

Type  Order No. 
11FSM2-CT 30111010
17FSM2-CT 30111020

Your Name (required)

Your Email (required)